72   Max Authentication Failures statistic reset on Controlled Station

Created: 06 Nov 2024

Status: Approval (Editoral)

Part: Part 5 (2013, Edition 2, TS)

Links:

Page: 72

Clause: 7.3.3.5

Paragraph: Table 30, Cell 24

Issue

On Controlling Station, the Max Authentication Failures statistic is reset whenever a valid Session Key Change Confirmation is received from the Outstation, while on Controlled Station the Max Authentication Failures statistic is not reset whenever a valid Session Key change has been received.

Proposal

On Controlled Station, the Max Authentication Failure statistic should be reset whenever a valid Session Key Change has been received.

Discussion Created Status
The statement "Reset Authentication Failures Statistic" shall be added in Table 30, Cell 24, in both columns C and E.
Note: This change is already done in IEC 62351-100-1:2018.
22 Nov 24 Approval (Editoral)
We needed to review it again.
We agreed that it is an editorial change.
22 Nov 24 Discussion (red)
Check if there are conformance test cases affected by this resolution 20 Nov 24 Conformance Test Preparation
This change is related to the management of a statistic counter, it does not affect the authentication mechanism or interoperability. 20 Nov 24 Analysis Of Compatibility
In the state machine, for the event described in Table 30, Cell 24, the directive "Reset Max Authentication Failure" shall be added in the Action columns C and E. 20 Nov 24 Verify Draft Implementation
Add the sentence "Reset Max Authentication Failures" in Table 30, Cell 24, Columns C and E. 20 Nov 24 Drafting Implementation
On Controlled Station, the Max Authentication Failure statistic shall be reset whenever a valid Session Key Change has been received. 20 Nov 24 Discussion (red)
This is an missed indication in Table 30, Cell 24, Columns C and E. 20 Nov 24 Accepted
I agree with the proposal. 07 Nov 24 Triage

 