34 TC-6.2.2: Transmission of ADSUCreated: 26 Dec 2023 Status: Approval (Future Improvement) Part: Part 100-1 (2018, Edition 1) Links: Page: 22 Clause: 6.2.2 Paragraph: Transmission of ADSU longer than the maximum lengt Issue Test Condition: DUT is a IEC 60870-5-104 slave implementation without File Transfer support. The DUT implementation considers the supported mandatory critical ASDU (commands) to be responded with ACTCON and ACT_TERM as non-critical (in base protocol), as defined in IEC 60870-5-7:2013 chapter 5.
Proposal Resolution: Mentioned test case should be Optional or Conditional to the PICS implementation