135 More expected actions need to be specified for test case 7.6.3.2.1Created: 22 Nov 2025 Status: Triage Part: Part 100-1 (2018, Edition 1) Links: Page: 77 Clause: 7.6.3.2 Resiliency test cases Paragraph: test case 7.6.3.2.1 Issue Handling of Reply Timer and pending Critical ASDU is not specified in the expected action list.
Proposal After sending S_CH_NA_1, DUT starts the Reply Timer and goes to Wait for Reply state. In the Wait for Reply state, if invalid reply is received, the Reply Timer should be cancelled and the pending Critical ASDU should be discarded.
Privacy | Contact | Disclaimer Tissue DB v. 25.7.7.1 |